Download a PDF version: 400 Amp (320) Underground Service on Panel (PDF)
General Information for Underground Services
- Member to supply conduit if underground service goes under a drive, conduit shall be 3-inch schedule 40 conduit
unless otherwise specified by engineer - Minimum size underground service is 200 Amp
- 400 Amp
- #2/0 Copper or #4/0 Aluminum out of meter base to means of disconnect
- 3-inch conduit to extend from bottom of meter base below grade 18 inches
- Grounding
- 2 ⅝-inch by 10-foot ground rods are required spaced at 6 feet apart and using #2 copper as the conductor
- Meter Height
- Meter base shall be installed 5 feet above finished grade
Entrance Location
No meter base or entrance shall be installed before a KV REMC engineer has checked the proposed location
The structure described below is to be furnished and installed by the member.